1 Scope
This document applies to two-wire, up to five-wire installation couplers , including earth, if provided, with a rated voltage up to and including 500 V AC or DC and a rated connecting capacity up to and including 10 mm 2 for permanent connection in electrical installations. Installation couplers with additional contacts for voltages other than mains voltages are outside the scope
of this document.
An installation coupler consists of an installation female connector and an installation male connector for permanent connection not intended to be engaged or disengaged under load nor to be engaged or disengaged
other than during first installation or during reconfiguration or maintenance of the
wiring system in which installation couplers have been installed. This means that installation couplers are only intended for infrequent use.
Installation couplers are not suitable for use in place of socket-outlet systems. Installation couplers are not suitable for use in place of devices for connecting luminaires (DCLs) according
to IEC 61995 (all parts) or in place of luminaire supporting couplers (LSCs).
Installation couplers complying with this document are suitable for use at ambient temperatures not normally
exceeding +40 °C, but their average over a period does not exceed +35°C, with a lower
limi...