1 Scope
This part of IEC 61000, which is informative in its nature, provides guidance on principles that can be
used as the basis for determining the requirements for the connection of disturbing installations to low voltage (LV) public power systems. For the purposes of this part of IEC 61000, a disturbing installation means an installation (which may be a load or a generator) that produces disturbances:
harmonics and/or interharmonics, voltage flicker and/or rapid voltage changes , and/or voltage unbalance. The primary objective is to provide guidance to system
operators or owners for engineering practices, which will facilitate the provision
of adequate service quality for all connected customer installations. In addressing installations, this report is not intended to replace
equipment standards for emission limits.
NOTE 1 In this report, low voltage (LV) refers to U n ≤1 kV.
This report addresses the allocation of the capacity of the system to absorb disturbances.
It does not address how to mitigate disturbances, nor does it address how the capacity
of the system can be increased.
This technical report only applies to installations connected to LV public power systems
that supply or may supply other LV loads or installations. It is intended to apply
to large installations exceeding a minimum size. This minimum size (S min ) is to be specified by the system operator or owner dependin...